Outdoor Substations
Indoor Substations
PRODUCTS >> INTERNATIONAL>> SWITCHGEAR>> SURGE ARRESTERS
Approvals : CPRI - India
Standards : IEC 99 - 4, 1991
S.No.
TYPE
REF.
RATED VOLTAGE
(kV)
SYSTEM
VOLTAGE
(kV)
INSULA-
TION
LEVEL
(kV/kVp)
NDC (kA)
ENERGY
CLASS
LIRV AT
NDC,
8/20 MICRO
SEC (kVp)
1
ZYP D 31
9
12
28 / 75
5
DIST
32
2
ZLA X 15C
9
12
28 / 75
10
30
3
ZLA X 25C
9
12
28 / 75
10
25
4
ZYA D 31
18
24
50 / 125
5
DIST
64
5
ZLA X 15C
18
24
50 / 125
10
56
6
ZLA X 15C
30
36
70 / 170
10
90
7
ZLA X 15C
60
72.5
140 / 325
10
175
8
ZLA X 25C
36
36
70 / 170
10
84
9
ZLA X 25C
72.5
72.5
140 / 325
10
165
10
ZLA X 25C
123
123
230 / 550
10
265
11
ZLA X 25C
145
145
275 / 650
10
350
12
ZLA X 25C
145
145
275 / 650
20
320
13
ZLA X 25C
245
245
460/ 1050
10
550/575
14
ZLA X 25C
245
245
460/ 1050
20
575/620
15
ZLA X 25C
420
420
630/ 1425
& 1050
20
975
*For solidly earth systems.
Other specifications ( Including LV ) are also feasible.
Standard value of creepage is 25 mm/kV