Indoor Substations
|
| PRODUCTS
>> INTERNATIONAL>> SWITCHGEAR>> INDUCTIVE
VOLTAGE TRANSFORMERS |
 |
 |
|
|
Approvals
: CPRI - India
Standards : IEC 186 - 1987, ANSI C93. 1, 1990. |
|
| Sno. |
Type
Ref. |
Rated
Voltage (kv) |
Insulation
Level (kV/kVp) |
Secondary
Voltage (V) |
No.
of Sec. WDG |
Simultaneous
Burden/Class |
|
1
|
CGV
|
24
|
50 / 125
|
100,110, 120,
|
3
|
120 VA/ 0.5
|
|
2
|
CGV
|
36
|
70 / 170
|
100,110, 120,
|
3
|
200VA / 0.5
|
|
3
|
CGV
|
52
|
95 / 250
|
100,110, 120,
|
3
|
200VA / 0.5
|
|
4
|
IVT
|
72.5
|
140 / 325
|
100,110,120,
|
3
|
200VA / 0.5
|
|
5
|
VEOT
|
123
|
230 / 550
|
100,110, 120,
|
3
|
500VA / 0.5
|
|
6
|
VEOT
|
145
|
275 / 650
|
100,110, 120,
|
3
|
500VA / 0.5
|
|
7
|
VEOT
|
245
|
460 / 1050
|
100,110, 120,
|
3
|
500VA / 0.5
|
| THE
ABOVE ARE TYPICAL VALUES. OTHER SPECS ARE
ALSO FEASIBLE.STD. VALUE OF CREEPAGE IS 25
mm/kV |
|
 |
|
 |
 |
|
|