Product Types
  PRODUCTS >> INTERNATIONAL>> LARGE MACHINES & RAIL PRODUCTS >> HV SYNC. GENERATORS
Specifications
 Output  : 1000 KVA - 8000 KVA
 Supply Voltage  : Three phase - 415 V, 3300V, 6600 V, 11000V
 Frequency  : At 60 Hz, 50 Hz, 25 Hz
 Insulation  : Class F ( Standard ), Class H ( Optional )
 Speed  : 1500 RPM, 1000 RPM, 750 RPM, 600 RPM, 500 RPM
 Enclosures  : SPDP ( IP23 ), CACW ( IP 44 ), CACA ( IP 44 )
 Bearings  : Single or double grease lubricated anti - friction bearings 
Oil lubricated white metal lined sleeve bearings
 Excitation  : Brushless Type
 Prime mover  : Diesel engine, steam turbine, hydro turbine, gas turbine
 Standards  : IS 4722, IEC 34 - 1, IEEE 115
Stator
 Frame   : Fabricated with Mild Steel
 Core  : Built up from low loss silicon steel laminations coated with varnish
Radial ventilation design for better cooling, no hot spots, low noise
 Winding  : Class "F" insulation
Rotor
 Shaft  : From steel forgong
 Poles  : Laminated / Solid
 Rotor hub  : Integral with shaft / fabricated from steel plates
 Pole fitment  : Bolted / Dove - tailed
 Pole coils  : Multilayer / Single Layer
 Insulation  : Class "F"
 Damper Winding  : Connected Copper Cage ( for laminated poles)
Bearings
 Anti - friction type  : For smaller rating
 Sleeve type  : For higher rating
 Bearing Insulation  : NDE side bearing is of insulated type
Terminal Boxes
  • Generally 1 each for Main and Neutral
  • Phase Segregated Terminal Box tested to withstand 43 kA for 0.25 seconds as optional
 AVR and Excitation System: Crompton Greaves offers a wide choice of AVR and Excitation System with the generators.
  • The Excitaion system mainly comprises of an Auto mode and a manual mode.
  • In Auto Mode the system is built to operate to work in solo mode / parallel with Grid mode
  • The Standard Excitation panel offers the following features:
    1. Electronic AVR capable of maintaining voltage regulations within ± 0.5%.
    2. Manual mode with hand operated variac
    3. Auto mode with motorised potentiometer along with local / remote selector switch.
    4. Quadrature droop feature for parallel operation with other generators.
    5. Overfluxing protection.
    6. Diode Failure indicator.
    7. Field Flashing facility.
    8. Exciter field Voltmeter, Ammeter and Generator volt meter.
    9. Indicating bulbs for Excitation ON / OFF, Manual mode ON, Auto Mode ON.
 The following Special Features are also offered whenever called for :
  1. Automatic Power Factor Controller for Grid
  2. Minimum Excitaion and Maximum Excitation limiter.
  3. Smooth and Automatic changeover from Auto to Manual with the help of Auto Tracking Unit.
  4. Null Balance Meter for changeover from Manual mode to Auto mode.
  5. Over Excitation and Under Excitation Relay.
  6. Over Voltage Relay.
  7. Additional Auto Channel.